Standard Fire Rated Access Door - 24 In x 36 In
- Buy 5 for CA$344.10 each and save 3%
- Buy 10 for CA$332.25 each and save 7%
The WB-FR Standard Fire Rated Access Door is designed for both wall and ceiling applications. For walls, this door has an Underwriters Laboratories (UL and ULC), 1-1/2 hour “B” label, with a maximum temperature rise of 250 degrees Celsius after 30 minutes for vertical wall installations. Warnock Hersey International; Pittsburgh, CA 1 hr rating for combustible floor/ ceiling applications. 3 Hr. rating for non-combustible floor/ceiling assembly. This door may be used in a 2-hour fire rated wall assembly. For fire rated ceilings, this door has been approved by Warnock Hersey International for 3 hours (*max. size to 24” x 36”). Intertek Spec. ID #57683.
Features
- Door and Trim - 18 ga. cold rolled steel.
- Box Return Frame - 16 ga. cold rolled steel.
- Insulation – 2 inches thick mineral wool contained within door cavity.
- Hinge - Fully concealed rod type hinge.
- Allows opening to 170 degrees.
- Latch - Self-latching direct-action latch, opposite hinge. Accepts both key and knurled knob, included with each door.
- Automatic Panel Closer - Standard on all doors.
- Inside Panel Release - Standard on all doors.
- Finish - White powder coat finish.
- Masonry Anchor Straps - Standard on all doors.
Available options (call for pricing)
- Mortise lock preparation
- Stainless steel #304 and #316 (#4 satin finish)
- Pemko hot smoke seal gasketing
- Custom sizes available
Ceiling Installation - To comply with current fire regulations, largest size acceptable is 24 inches x 36 inches.
Material Specifications | Cold Rolled Steel |
---|---|
Warnock Hersey Mark | YES |
ULC Approval | YES |
Dimensions, Exterior Width | 24 Inches - Door |
Dimensions, Exterior Height | 36 Inches - Door |
Net Weight | Shipping Weight - 46 Lbs |